Model A1000 - Insulated Pipe Support - Regular Duty |
< Back to Commerical & Light Industrial Types
Oper. Temp°F |
Mult. Factor "F" |
500
750
1000
1200 |
.90
.75
.50
.30 |
Table III |
Hardware Sold Separately - Note: For higher load ratings, see A3000, A9000. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "A" in Table II. To develop maximum load rating, use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I.
To obtain load ratings for operating temperatures of 500°F and higher, multiply load rating by factor "F" in Table III. |
Pipe Size |
Maximum Load Rating (lb.) |
On Flat Surface (a) (c) |
In Clevis Hanger (b) (c) |
| |
35 40 60 |
40
45
65 |
1 1/4
1 1/2
2 |
70
100
125 |
80
110
140
|
2 1/2
3
3 1/2 |
150
180
225 |
200
250
300 |
4
5
6 |
270
350
400 |
350
450
550 |
8
10
12 |
450
500
550 |
750
1000
1200 |
14
16
18 |
575
600
625 |
1400
1600
1800 |
20
24 |
675
750 |
2000
2300
|
TABLE I |
|
Iron Pipe Size |
Insulation Thickness |
Copper Tubing Size O.D. |
1/2 |
3/4 |
1 |
1 1/2 |
2 |
2 1/2 |
3 |
3 1/2 |
4 |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
1/2 - 1 1/2 |
4 |
24 |
4 |
24 |
4 |
24 |
4 |
24 |
4 |
24 |
4 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
5/8 - 1 5/8 |
2 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
2 1/8 |
2 1/2 - 4 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
20 |
9 |
20 |
9 |
20 |
2 5/8 - 4 1/8 |
5 |
|
|
|
|
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
20 |
9 |
20 |
9 |
20 |
5 1/8 |
6 - 7 |
|
|
|
|
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
16 |
9 |
16 |
9 |
16 |
6 1/8 |
8 - 10 |
|
|
|
|
|
|
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
8 1/8 - 10 1/8 |
12 - 18 |
|
|
|
|
|
|
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 1/8 |
20 - 24 |
|
|
|
|
|
|
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
|
TABLE II "B" = gauge of sheet metal jacket |
Application:
Model A1000 is designed for use on:
- Hot Water
- Cold Water
- Dual Temperature
- Vacuum
- Steam
- Chilled Water
- Gas
- Air
Intended for Installation on:
- Flat Surfaces
- Band, ring or clevis pipe hanger
Temperature Range: +40°F to +1200°F
Note: Up to 1700°F available upon request. |
Features
- Compact
- Easy Installation
- Eliminates welding to pipe
- Overlapping galvanized sheet metal jacket
- Minimizes heat loss and/or condensation
- Copper tubing sizes available
- Other I.D.'s and/or O.D.'s available on request
- Clamps available (see G-Series)
Performance Test Results on File: Available upon request. |
Material Data:
- A1000: Applicable PSI spec. doc.: No. 205
- Insulation: Calcium Silicate asbestos-free, treated with water repellant.
- Jackets: Galvanized Steel ASTMA-527
- Glue: Industrial contact adhesive
Formal Submittal Sheets Available |
|
| |
|
|