Model A3000 - Insulated Pipe Support - Extra Heavy Bottom Jacket |
< Back to Commerical & Light Industrial Types
Oper. Temp°F |
Mult. Factor "F" |
500
750
1000
1200 |
.90
.75
.50
.30 |
Table III |
Hardware Sold Separately - Note: For higher load ratings, see A5000, A9000. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "A" in Table II. Divide "A" in Table II by 6 to find maximum allowable travel on pipe roll (+/- from centered position). To develop maximum load rating, use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I.
To obtain load ratings for operating temperatures of 500°F and higher, multiply load rating by factor "F" in Table III. |
Pipe Size |
Maximum Load Rating (lb.) |
On Flat Surface (a) (c) |
On Pipe Roll (b) (d) |
In Clevis Hanger (b) (c) |
| |
40
45
65 |
35
40
60 |
45
50
70 |
1 1/4
1 1/2
2 |
80
110
140 |
70
100
125 |
90
120
155
|
2 1/2
3
3 1/2 4 |
165
200
250
300 |
150
180
225
270 |
220
275
325 375 |
5
6 |
400
450 |
See
A5000 |
475
575 |
8
10
12 |
500
525
575 |
800
1100
1300 |
14
16
18 |
600
625
650 |
1500
1700
1900 |
20
24 |
700
775 |
2100
2400
|
TABLE I |
|
Iron Pipe Size |
Insulation Thickness |
Copper Tubing Size O.D. |
1/2 |
3/4 |
1 |
1 1/2 |
2 |
2 1/2 |
3 |
3 1/2 |
4 |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
1/2 - 1 1/2 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
5/8 - 1 5/8 |
2 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
2 1/8 |
2 1/2 - 4 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
20 |
9 |
20 |
9 |
20 |
2 5/8 - 4 1/8 |
5 |
|
|
|
|
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
20 |
9 |
20 |
9 |
20 |
5 1/8 |
6 - 7 |
|
|
|
|
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
16 |
9 |
16 |
9 |
16 |
6 1/8 |
8 - 10 |
|
|
|
|
|
|
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
8 1/8 - 10 1/8 |
12 - 18 |
|
|
|
|
|
|
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 1/8 |
20 - 24 |
|
|
|
|
|
|
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
|
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. or top jacket) |
Application:
Model A3000 is designed for use on:
- Cold Water
- Hot Water
- Chilled Water
- Dual Temperature
- Steam
- Air
- Gas
- Vacuum
Intended for Installation on:
- Flat Surfaces
- Pipe Rolls
- Band, ring or clevis pipe hangers
Temperature Range: +40°F to +1200°F
Note: Up to 1700°F available upon request. |
Features
- Compact
- Easy Installation
- Eliminates welding to pipe
- Overlapping galvanized sheet metal jacket
- Minimizes heat loss and/or condensation
- Double thickness bottom jacket for added structural strength and abrasive wear resistance
- Copper tubing sizes available
- Other I.D.'s and/or O.D.'s available on request
- Clamps available (see G-Series)
Performance Test Results on File: Available upon request. |
Material Data:
- A3000: Applicable PSI spec. doc.: No. 205
- Insulation: Calcium Silicate asbestos-free, treated with water repellant.
- Jackets: Galvanized Steel ASTMA-527
- Glue: Industrial contact adhesive
Formal Submittal Sheets Available |
|
| |
|
|