Model A9000 - Insulated Pipe Support - Heavy Duty for Use with Rod Hangers |
< Back to Commerical & Light Industrial Types
Hardware Sold Separately - Note: For higher load ratings, see D1000, D3000. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice.
To develop maximum load rating, use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I.
|
Pipe Size |
Maximum Load Rating (lb.) |
In Clevis Hanger (a) |
| |
50
55
80 |
1 1/4
1 1/2
2 |
100
130
175
|
2 1/2
3
3 1/2 |
250
300
350
|
4 5
6 |
400 550
600 |
8
10
12 |
900
1200
1450 |
14
16
18 |
1650
1900
2150 |
20
24 |
2400
2750
|
TABLE I |
|
Iron Pipe Size |
Insulation Thickness |
Copper Tubing Size O.D. |
1/2 |
3/4 |
1 |
1 1/2 |
2 |
2 1/2 |
3 |
3 1/2 |
4 |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
A |
B |
1/2 - 1 1/2 |
4 |
24 |
4 |
24 |
4 |
24 |
4 |
24 |
4 |
24 |
4 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
5/8 - 1 5/8 |
2 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
6 |
24 |
2 1/8 |
2 1/2 - 4 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
20 |
9 |
20 |
9 |
20 |
2 5/8 - 4 1/8 |
5 |
|
|
|
|
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
20 |
9 |
20 |
9 |
20 |
5 1/8 |
6 - 7 |
|
|
|
|
6 |
20 |
6 |
20 |
6 |
20 |
6 |
20 |
9 |
16 |
9 |
16 |
9 |
16 |
6 1/8 |
8 - 10 |
|
|
|
|
|
|
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
9 |
16 |
8 1/8 - 10 1/8 |
12 - 18 |
|
|
|
|
|
|
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 |
16 |
12 1/8 |
20 - 24 |
|
|
|
|
|
|
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
18 |
16 |
|
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. or top jacket) |
Application:
Model A9000 is designed for use on:
- Cold Water
- Hot Water
- Chilled Water
- Dual Temperature
- Steam
- Air
- Gas
- Vacuum
Intended for Installation on:
- Flat Surfaces, see A7000
- Pipe Rolls, see A8000
- Band, ring or clevis pipe hangers
Temperature Range: +40°F to +1200°F
Note: Up to 1700°F available upon request. |
Features
- Compact
- Easy Installation
- Eliminates welding to pipe
- Overlapping galvanized sheet metal jacket
- Minimizes heat loss and/or condensation
- Insulating structural inserts for load transfer
- Copper tubing sizes available
- Other I.D.'s and/or O.D.'s available on request
Performance Test Results on File: Available upon request. |
Material Data:
- A9000: Applicable PSI spec. doc.: No. 205
- Insulation: Calcium Silicate asbestos-free, treated with water repellant.
- Jackets: Galvanized Steel ASTMA-527
- Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant
- Glue: Industrial contact adhesive
Formal Submittal Sheets Available |
|
| |
|
|