Model E2100 - Insulated Pipe Riser Clamps for Upward or Downward Loads |
|
a. If thrust plate thickness "B" is greater than pipe wall thickness, consult factory.
b. One pair thrust plates supplied loose for field welding, top only.
Note: For higher load ratings, see: E2200.
Iron Pipe Size |
load lb.
|
A |
B |
C |
D |
E |
Insul Thk. = 1" |
Insul Thk. = 2" |
Insul Thk. = 3" |
Insul Thk. = 4" |
F |
G |
H |
F |
G |
H |
F |
G |
H |
F |
G |
H |
2
2 1/2
3 4 |
500
600
800
1200 |
0.63
0.63
0.63 0.63 |
0.38
0.38
0.38
0.38 |
0.38 x 3.00
0.38 x 3.00
0.38 x 3.00
0.38 x 3.00 |
1.50
1.50
1.50 1.50 |
0.625
0.625
0.625 0.625 |
3.94
4.19
4.47
5.00 |
6.19
6.44
6.72
7.25 |
5.38
5.88
6.44
7.50 |
5.00
5.50
5.50
6.00 |
7.25
7.75
7.75
8.25 |
7.50
8.50
8.50
9.50 |
6.00
6.50
6.50
7.06 |
8.25
8.75
8.75
9.31 |
9.50
10.50
10.50
11.63 |
7.06
7.56
7.56
8.06 |
9.31
9.81
9.81
10.31 |
11.63
12.63
12.63
13.63 |
5
6
8
10 |
1600
2000
2600 3200 |
0.63
0.63
0.63
0.88
|
0.38
0.38
0.50
0.50
|
0.38 x 4.00
0.38 x 4.00
0.50 x 4.00
0.50 x 5.00
|
2.00
2.00
2.00
3.00
|
0.625
0.625
0.625
0.625
|
5.50
6.00
7.31
8.31
|
7.75
8.25
9.81
10.81
|
8.50
9.50
11.88
13.88
|
6.50
7.06
8.31
9.44
|
8.75
9.31
10.81
11.94
|
10.50
11.63
13.88
16.13
|
7.56
8.06
9.44
10.44
|
9.81
10.31
11.94
12.94
|
12.63
13.63
16.13
18.13
|
8.69
9.19
10.44
11.44
|
10.94
11.44
12.94
13.94
|
14.88
15.88
18.13
20.13
|
12
14
16
18
|
3400
4000
4600
5000
|
0.88
0.88
0.88
0.88
|
0.50
0.50
0.50
0.50
|
0.50 x 5.00
0.50 x 5.00
0.50 x 6.00
0.50 x 6.00
|
3.00
3.00
4.00
4.00
|
0.625
0.75
0.75
0.75
|
9.44
10.06
11.06
12.06
|
11.94
12.69
13.69
14.69
|
16.13
17.13
19.13
21.13
|
10.44
11.06
12.06
13.06
|
12.94
13.69
14.69
15.69
|
18.13
19.13
21.18
23.13
|
11.44
12.06
13.06
14.06
|
13.94
14.69
15.69
16.69
|
20.13
21.13
23.13
25.13
|
12.44
13.06
14.06
15.06
|
14.94
15.69
16.69
17.69
|
22.13
23.13
25.13
27.13
|
20
24
|
5400
5600
|
0.88
0.88
|
0.50
0.50
|
0.50 x 6.00
0.50 x 6.00
|
4.00
4.00
|
0.75
0.75 |
13.06
15.06 |
15.69
17.69 |
23.13
27.13
|
14.06
16.06
|
16.69
18.69
|
25.13
29.13
|
15.06
17.06
|
17.69
19.69
|
27.13
31.13
|
16.06
18.06
|
18.69
20.69
|
29.13
33.13 |
|
|
Application:
Model E2100 through E2130 are designed for use on:
- Cold Water
- Hot Water
- Chilled Water
- Dual Temperature
- Steam
- Air
- Gas
- Vacuum
Intended for installation on:
- vertical runs of insulated pipe with upward and/or downward load.
Other:
- For handling downward loads only, see E1100.
Temperature Range: +40°F to +1200°F |
Features
- All pipe sizes
- Easy Installation
- Positive stop - axially downward.
- May be supported from below or above.
- Overlapping galvanized sheet metal jacket
- Insulating structural inserts for load transfer
- Other I.D.'s and/or O.D.'s available on request
- Eliminates condensation sweating on chilled water risers
Performance Test Results on File: Available upon request. |
Material Data:
- E2100 - E2130 : Applicable PSI spec. doc.: No. 206
- Steel Top Thrust Plates
- Model E2100: A25 Carbon-Steel
- Model E2110: A387 Gr.11 Chrome-Moly
- Model E2120: A515 Gr.70 Carbon Silicon
- Model E2130: A304L Stainless Steel
- Insulation: Calcium Silicate - Asbestos-free, treated with a water repellant.
- Jackets: Galvanized Steel ASTM-527
- Glue: Industrial contact adhesive
- Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant.
- Steel Straps: Carbon Steel ASTM A-36
- Fasteners: ASTM A-307 Plated
- Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets Available |
| |
|
|
|
| |
|
|